Adams – Flamingo Spec Rough – Logan
April 12, 2022 @ 7:00 am - 3:30 pm
Contract
punch list;
Strap island conduit at refrigerator
Hood circuit can’t be in center has to be to the right
Junction box for island has to be grounded
Do not change this one but wires in attic have to be run next to rat runs to protect from physical damage equal to the height of the cable if more than 2’ head space and permanent pull down stairs/ladder provide access to the attic. If only a lift out panel then must be protected within 6′ of the access.
Need outlet on wall to left of closet front room
Stud guards back bedroom rear wall
Need outlet on living room wall below TV (TV outlet is above 66”)
Need outlet on rear wall right side of slider
Too much foam at 2 gang dining/nook (pushed switch box out of wall)
Same as above in master bedroom at outlets
Smoke detector master bedroom has to be in high ceiling
Foam cable penetrations to exterior at master closet
Dryer outlet has to be to the right or left of dryer space, center is for the duct pipe
Stub air handler wire out or low garage ceiling se we don’t have to flex protect so much wire on trim
Pancake boxes for coach lights
1 gang bracket boxes for exterior receps (stucco guys will mud right over cutins)
Light junction in entry won’t work stub wire only (they will need to build a block for us to mount to)
build service the cut in panel